H1-01
to 6
Setting
12
Forward Jog
13
Reverse Jog
14
Fault Reset (factory default, H1-02)
15
Fast-Stop
16
Motor 2 Select
17
Fast-Stop (Closed, motor decels by C1-09)
<1110>
18
Timer Function
19
PID Disable
1A
Multi-Accel/Decel 2
1B
Program Lockout
1C
Trim Control Increase
1D
Trim Control Decrease
1E
Reference Sample Hold
1F
Terminal 13/14 Switch
20-2F
External Fault (factory default, H1-01)
30
Closed: PID Integral is Reset
31
Closed: PID Integral Value is Held
60
DC Injection Activate
61
Speed Search 1
62
Speed Search 2
63
Energy Saving Command
64
Speed Search 3
65
KEB Ridethrough N.C.
66
KEB Ridethrough N.O
71
Speed/Torque Control Change
72
Zero Servo Command
77
ASR Gain Switch
· 3-Wire Control (setting: "0")
When H1-__ is set to "0", 3-wire control is enabled. The terminal set to "0" becomes the FWD/REV
run command.
Figure 31 Terminal Function at 3-Wire Sequence Selection (H1-__ = "0")
VS-616G5 Programming Manual
Function
V/f
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
<1110>
√
√
√
√
√
√
√
−
−
−
S1
Run Command
(Run when "Closed")
S2
Stop Command
(Stop when "Open")
S3
FWD/REV Run Selection
(FWD Run when "Open"
SC
REV Run when "Closed")
Section H: Control Circuit Terminals
Control Method (A1-02)
Open Loop
V/f w/ PG
Flux Vector
Vector
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
−
√
−
√
√
−
√
√
√
√
√
√
−
−
−
−
−
−
H1 Digital Inputs
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
Reference
Page
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
−
−
−
√
√
√
√
√
√
77