Reducing The Attenuation Of Ripple Control Signals; Setting Sma Optitrac Global Peak - SMA SUNNY TRIPOWER 15000TL Operating Manual

Hide thumbs Also See for SUNNY TRIPOWER 15000TL:
Table of Contents

Advertisement

8 Configuration
Procedure:
1. Ensure that the firmware version of the inverter is at least 2.62.04.R. If necessary, carry out a
firmware update.
2. Select the parameter Fallback act power lmt P in % of WMax for absent act power lmt
and set the required percentage.
3. Select the parameter Operating mode for absent plant control and set to Use fallback
setting.
8.6

Reducing the Attenuation of Ripple Control Signals

By setting certain parameters, the attenuation of three-phase parallel ripple control frequencies
ranging from 1,000 Hz to 1,100 Hz can be avoided. The parameters must only be set in
consultation with the responsible grid operator.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.3 "Changing Operating Parameters", page 40).
Requirement:
☐ The firmware version of the inverter must be at least 2.62.04.R.
Procedure:
• Set the following parameters:
Parameter
name for
RS485
RplDet-NBS-Gain Ripple control signal detection, am-
RplDet-NBS-
Damp
RplDet-NBS-Hz
8.7

Setting SMA OptiTrac Global Peak

For partially shaded PV modules, you should set the interval at which the inverter is to optimize the
MPP of the PV system.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.3 "Changing Operating Parameters", page 40).
42
STP15-17TL-10-BE-en-10
Parameter name for
BLUETOOTH or Speedwire/We-
bconnect
plification of narrow-band backup
Ripple control signal detection, at-
tenuation of narrow-band backup
Ripple control signal detection, fre-
quency of the narrow-band backup
SMA Solar Technology AG
Unit
Range Value to be set
V/A
0 to -10 -9
p.u.
-
0.1
Hz
1,000
Must be specified
to
by the grid oper-
1,100
ator
Operating Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny tripower 17000tl

Table of Contents