FC 300 Operating Instructions

Fuses

"
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in
an installation, switch gear, machines etc., must be shortcircuit and overcurrent protected
according to the national/international regulations.
Short circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard.
Danfoss recommends using the fuses mentioned below to protect service personnel or other
equipment in case of an internal failure in the drive. The frequency converter provides full short
circuit protection in case of a short-circuit on the motor output.
Over current protection:
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation.
The frequency converter is equipped with an internal over current protection that can be used
for upstream overload protection (UL-applications excluded). See par. 4-18. Moreover, fuses or
circuit breakers can be used to provide the over current protection in the installation. Over current
protection must always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable of supplying a maximum of
100,000 A
(symmetrical), 500 V maximum.
rms
Non UL compliance
If UL/cUL is not to be complied with, we
recommend using the following fuses, which will
ensure compliance with EN50178:
In case of malfunction, not following the
recommendation may result in unnecessary
damage of the frequency converter.
UL Compliance
200-240 V
FC 30X
Bussmann
kW
Type RK1
K25-K75
KTN-R10
1K1-2K2
KTN-R20
3K0-3K7
KTN-R30
22
How to Install
Bussmann
Bussmann
Type J
Type T
JKS-10
JJN-10
JKS-20
JJN-20
JKS-30
JJN-30
MG.33.A7.02 - VLT is a registered Danfoss trademark
FC 30X
Max. fuse size
K25-K75
10A
1K1-2K2
20A
3K0-3K7
32A
K37-1K5
10A
2K2-4K0
20A
5K5-7K5
32A
11K
63A
15K
63A
18K
63A
22K
80A
1) Max. fuses - see national/international
regulations for selecting an applicable fuse size.
SIBA
Littel fuse
Type RK1
Type RK1
5017906-010
KLN-R10
5017906-020
KLN-R20
5012406-032
KLN-R30
Voltage
Type
1)
200-240 V
type gG
1)
200-240 V
type gG
1)
200-240 V
type gG
1)
380-500 V
type gG
1)
380-500 V
type gG
1)
380-500 V
type gG
1)
380-500 V
type gG
1)
380-500 V
type gG
1)
380-500 V
type gG
1)
380-500 V
type gG
Ferraz-
Ferraz-
Shawmut
Shawmut
Type CC
Type RK1
ATM-R10
A2K-10R
ATM-R20
A2K-20R
ATM-R30
A2K-30R