Nec And Ul Compliance - GE AF-600 FP Operating Instructions Manual

Fan and pump drive 460v/575v 150hp and above
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Electrical Installation

3.1.15 NEC and UL Compliance

Fuses or Circuit Breakers are mandatory to comply with NEC 2009. We recommend using a selection of the following
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 600V
depending on the drive voltage rating. With the proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
AF-600 1-
AF-600 3-
phase
phase
Bussmann
Power
Power
HP
HP
Type RK1
1
KTN-R-10
2
KTN-R-15
2
3
KTN-R-20
3
5
KTN-R-30
5
7.5-10
KTN-R-50
7.5
15
KTN-R-60
10
20
KTN-R-80
25-30
KTN-R-125
20
40
KTN-R-150
30
50
KTN-R-200
60
KTN-R-250
Table 3.8 200-240V
AF-600 1-
AF-600 3-
phase
phase
Power
Power
HP
HP
1
5017906-010
2
5017906-016
2
3
5017906-020
3
5
5012406-032
5
7.5-10
5014006-050
7.5
15
5014006-063
10
20
5014006-080
25-30
2028220-125
20
40
2028220-150
30
50
2028220-200
60
2028220-250
Table 3.9 200-240V
AF-600 FP High Power Operating Instructions
Recommended max. fuse
Bussmann
Bussmann
1)
Type J
JKS-10
JKS-15
JKS-20
JKS-30
KS-50
JKS-60
JKS-80
JKS-125
JJN-125
JKS-150
JJN-150
JKS-200
JJN-200
JKS-250
JJN-250
Recommended max. fuse
SIBA
Littel fuse
Type RK1
Type RK1
KLN-R-10
KLN-R-15
KLN-R-20
KLN-R-30
KLN-R-50
KLN-R-60
KLN-R-80
KLN-R-125
KLN-R-150
KLN-R-200
KLN-R-250
Bussmann
Type T
Type CC
JJN-10
FNQ-R-10
JJN-15
FNQ-R-15
JJN-20
FNQ-R-20
JJN-30
FNQ-R-30
JJN-50
-
JJN-60
-
JJN-80
-
-
-
-
-
Ferraz-
Shawmut
Type CC
ATM-R-10
ATM-R-15
ATM-R-20
ATM-R-30
-
-
-
-
-
-
-
Bussmann
Bussmann
Type CC
Type CC
KTK-R-10
LP-CC-10
KTK-R-15
LP-CC-15
KTK-R-20
LP-CC-20
KTK-R-30
LP-CC-30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Ferraz-
Shawmut
3)
Type RK1
A2K-10-R
A2K-15-R
A2K-20-R
A2K-30-R
A2K-50-R
A2K-60-R
A2K-80-R
A2K-125-R
A2K-150-R
A2K-200-R
A2K-250-R
3
3
25