Fan and pump drive 460v/575v 150hp and above
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

General Specifications
Mains Supply 3 x 380 - 480 VAC
7
7
Max. input current
118
AF-600 FP High Power Operating Instructions
Typical Shaft output at
400 V [kW]
Typical Shaft output at
460 V [HP]
Unit Size IP21
Unit SizeIP54
Unit Size IP00
Output current
Continuous
(at 400 V) [A]
Intermittent (60 sec
overload)
(at 400 V) [A]
Continuous
(at 460 V) [A]
Intermittent (60 sec
overload)
(at 460 V) [A]
Continuous KVA
(at 400 V) [KVA]
Continuous KVA
(at 460 V) [KVA]
Continuous
(at 400 V ) [A]
Continuous
(at 460 V) [A]
Max. cable size, mains,
motor and load share
(4x500 mcm)
2
2)
[mm
(AWG
)]
Max. external pre-fuses
1
[A]
Estimated power loss
4)
at rated max. load [W]
Weight,
Unit Size IP21, IP 54 [kg]
Weight,
Unit Size IP00 [kg]
4)
Efficiency
Output frequency
Heatsink overtemp. trip
Power card ambient trip
315
355
450
500
51
51
51
51
52
52
600
658
660
724
540
590
594
649
416
456
430
470
590
647
531
580
4x240
4x240
(4x500 mcm)
700
900
7630
7701
263
270
221
234
0 - 600 Hz
95 °C
68 °C
400
600
51
51
52
745
820
678
746
516
540
733
667
4x240
4x240
(4x500 mcm)
(4x500 mcm)
900
8879
272
236
0.98
450
600
51
51
52
800
880
730
803
554
582
787
718
900
9428
313
277