Ce Compliance - GE AF-650 GP Operating Instructions Manual

Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Specifications

10.3.2 CE Compliance

Fuses or Circuit Breakers are mandatory to comply with IEC 60364. GE recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V,
or 600V depending on the drive voltage rating. With the proper fusing the drive short circuit current rating (SCCR) is
100,000 Arms.
AF-650 GP 3-phase
Recommended fuse size
[HP]
IP20 / Open Chassis
1/3
1/2
1
2
3
5
7,5
10
15
20
25
30
40
50
Table 10.1 200-240V. IP20 / Open Chassis
AF-650 GP 3-phase
Recommended fuse size
[HP]
IP55 / Nema 12 and IP66 / Nema 4
1/3
1/2
1
2
3
5
7,5
10
15
20
25
30
40
50
Table 10.2 200-240V. IP55 / Nema 12 and IP66 / Nema 4
AF-650 GP Operating Instructions
Recommended max fuse
gG-16
gG-20
gG-50
gG-80
gG-125
gG-125
gG-150
aR-160
aR-200
aR-250
Recommended max fuse
gG-20
gG-63
gG-80
gG-100
gG-125
gG-160
aR-160
aR-200
aR-250
Recommended circuit breaker
gG-25
PKZM0-25
gG-32
gG-63
PKZM4-50
NZMB1-A100
NZMB2-A200
aR-160
aR-200
NZMB2-A250
aR-250
Recommended circuit breaker
gG-32
PKZM0-25
gG-80
PKZM4-63
NZMB1-A100
NZMB2-A200
aR-160
aR-200
NZMB2-A250
aR-250
Max trip level
[A]
25
50
100
150
250
Max trip level
[A]
10
10
25
63
100
160
250
77

Hide quick links:

Advertisement

Table of Contents
loading