GE AF-600 FP Operating Instructions Manual page 116

Fan and pump drive 460v/575v 150hp and above
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

General Specifications
Digital output:
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Max. output current (sink or source)
Max. load at frequency output
Max. capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output:
Terminal number
Max. load
The 24V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs:
Programmable relay outputs
Relay 01 Terminal number
1)
Max. terminal load (AC-1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
(Inductive load @ cosφ 0.4)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
(Inductive load)
Relay 02 Terminal number
1)
Max. terminal load (AC-1)
on 4-5 (NO) (Resistive load)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 4-5 (NO) (Resistive load)
1)
Max. terminal load (DC-13)
on 4-5 (NO) (Inductive load)
1)
Max. terminal load (AC-1)
on 4-6 (NC) (Resistive load)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 4-6 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
on 4-6 (NC) (Inductive load)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300V AC 2A
Control card, 10 V DC output:
Terminal number
Output voltage
Max. load
The 10V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics:
Resolution of output frequency at 0 - 1000Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed accuracy (open loop)
All control characteristics are based on a 4-pole asynchronous motor
AF-600 FP High Power Operating Instructions
2)3)
Max. error: 0.1% of full scale
1-3 (break), 1-2 (make)
240V AC, 0.2 A
4-6 (break), 4-5 (make)
240V AC, 0.2 A
240V AC, 0.2A
24V DC, 0.1 A
24V DC 10mA, 24V AC 20mA
overvoltage category III/pollution degree 2
1:100 of synchronous speed
30 - 4000 rpm: Maximum error of ±8 rpm
2
1)
27, 29
0 - 24V
40mA
1 kΩ
10nF
0Hz
32kHz
12 bit
12, 13
200mA
7
7
2
240V AC, 2A
60V DC, 1A
24V DC, 0.1A
400V AC, 2 A
80V DC, 2 A
24V DC, 0.1A
240V AC, 2 A
50V DC, 2 A
50
10.5V±0.5V
25mA
+/- 0.003Hz
≤ 2ms
115

Hide quick links:

Advertisement

Table of Contents
loading