Warnings and Alarms
ALARM 247, Power card temperature
This alarm is only for 6x unit size drives. It is equivalent to
Alarm 69. The report value in the alarm log indicates
which power module generated the alarm:
1 = left most inverter module.
2 = middle inverter module in 62 or 64 drive.
2 = right inverter module in 61 or 63 drive.
3 = right inverter module in 62 or 64 drive.
5 = rectifier module.
ALARM 248, Illegal power section configuration
This alarm is only for 6x unit size drives. It is equivalent to
Alarm 79. The report value in the alarm log indicates
which power module generated the alarm:
1 = left most inverter module.
2 = middle inverter module in 62 or 64 drive.
2 = right inverter module in 61 or 63 drive.
3 = right inverter module in 62 or 64 drive.
8
8
5 = rectifier module.
ALARM 250, New spare part
The power or switch mode power supply has been
exchanged. The frequency converter model number must
be restored in the EEPROM. Remember to select 'Save to
EEPROM' to complete.
ALARM 251, New model number
The frequency converter has a new model number.
134