Cable All Devices
Attach cables using the diagrams in this section as a guide. Connect a 4-pole captive screw connector to each end of the cable,
wiring both ends as shown in figure 15. In most cases the EBPs are powered by the IPCP Pro control processor that provides the
eBUS signal. Power is carried on the V+ pin of each eBUS connection.
The four connectors are:
+V — carries 12 VDC power from the controller, active hub, or power supply
+S — carries the positive data signal
-S — carries the negative data signal
G — ground
Extron STP20-2/1000 or STP20-2P/1000 cable is recommended for eBUS connections.
+12 VDC
+ Signal
- Signal
Ground
Basic eBUS Connector Wiring and Cable Color Code
Figure 15.
For long cable runs, category cable can provide a convenient option for eBUS signals. For these applications, compatible 4-pole
captive screw to RJ-45 adapters are available at www.extron.com.
Extron recommends using shielded CAT6 cable.
NOTES:
The two eBUS blocks are interchangeable: either block can be used to connect the unit to a controller or EBDB and
either can be used to daisy-chain the unit to another EBP.
Connect up to eight eBUS endpoint devices for each IPCP Pro control processor.
Wire the connectors in the same way at both ends.
See the eBUS Technical Reference Guide (available at www.extron.com) for information about the maximum cable
distance and power requirements for your eBUS system.
Do NOT power an EBP from more than one power source.
ATTENTION:
Always use a power supply supplied or specified by Extron. Use of an unauthorized power supply voids all regulatory
compliance certification and may cause damage to the supply and the unit.
Utilisez toujours une source d'alimentation fournie par Extron. L'utilisation d'une source d'alimentation non autorisée
annule toute conformité réglementaire et peut endommager la source d'alimentation ainsi que l'unité.
If not provided with a power supply, this product is intended to be supplied by a UL Listed power source marked
"Class 2" or "LPS" and rated output 12 VDC, minimum 1.0 A.
Si ce produit ne dispose pas de sa propre source d'alimentation électrique, il doit être alimenté par une source
d'alimentation certifiée UL de classe 2 ou LPS et paramétré à 12 VDC et 1,0 A minimum.
Unless otherwise stated, the AC/DC adapters are not suitable for use in air handling spaces or in wall cavities.
Sauf mention contraire, les adaptateurs AC/DC ne sont pas appropriés pour une utilisation dans les espaces
d'aération ou dans les cavités murales.
The installation must always be in accordance with the applicable provisions of National Electrical Code ANSI/
NFPA 70, article 725 and the Canadian Electrical Code part 1, section 16. The power supply shall not be permanently
fixed to building structure or similar structure.
Cette installation doit toujours être en accord avec les mesures qui s'applique au National Electrical Code ANSI/
NFPA 70, article 725, et au Canadian Electrical Code, partie 1, section 16. La source d'alimentation ne devra pas être
fixée de façon permanente à une structure de bâtiment ou à une structure similaire.
Red
Green
White
Black
Drain Wires
Product Category
+V
+S
-S
G
11