Protection and features
Electronic thermal motor protection motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips in case of overtem-
perature.
The adjustable frequency drive is protected against short-circuits between motor terminals U, V, W.
If a motor phase is missing, the adjustable frequency drive trips and issues an alarm.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
Line power supply (L1, L2, L3)
Supply voltage
Supply voltage
Supply voltage
Supply frequency
Max. temporary imbalance between line phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H1-H5, I2, I3, I4
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H6-H8, I6-I8
Environment according to EN 60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V
maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
Cable lengths and cross-sections
Max. motor cable length, shielded/armored (EMC-compliant installation)
Max. motor cable length, unshielded/unarmored
Max. cross-section to motor, line power*
Cross-section DC terminals for filter feedback on enclosure frame H1-H3, I2, I3, I4
Cross-section DC terminals for filter feedback on enclosure frame H4-H5
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Minimum cross-section to control terminals
*See 1.7.2 Line Power Supply 3x380–480 V AC for more
information
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic '0' PNP
Voltage level, logic '1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
®
VLT
HVAC Basic Drive Quick Guide
®
MG18A422 - VLT
is a registered Danfoss trademark
200–240 V ±10%
380–480 V ±10%
525–600 V ±10%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
Max. 2 times/min.
Max. 1 time/min.
overvoltage category III/pollution degree 2
0–100% of supply voltage
0–200 Hz (VVC
plus
), 0–400 Hz (u/f)
See 1.7.5 EMC Test Results
4 mm
16 mm
2.5 mm
2.5 mm
0.05 mm
1
1
50/60 Hz
(>0.98)
Unlimited
0.05–3,600 s
165 ft [50m]
2
/11 AWG
2
/6 AWG
2
/14 AWG)
2
/14 AWG)
2
/30 AWG
4
18, 19, 27, 29
PNP or NPN
0–24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
1-45