Quick Guide
1
1
No & Name
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal
Speed
1-26 Motor Cont. Rated
Torque
1-29 Automatic Motor
Adaption (AMA)
1-30 Stator Resistance
(Rs)
1-37 d-axis Inductance
(Ld)
1-39 Motor Poles
1-40 Back EMF at 1000
RPM
1-73 Flying Start
1-73 Flying Start
3-02 Minimum Reference -4,999–4,999
3-03 Maximum Reference -4,999–4,999
3-41 Ramp 1 Ramp Up
Time
3-42 Ramp 1 Ramp
Down Time
4-12 Motor Speed Low
Limit [Hz]
4-14 Motor Speed High
Limit [Hz]
4-19 Max Output
Frequency
5-40 Function Relay [0]
Function relay
1-24
®
VLT
HVAC Basic Drive Quick Guide
Range
50.0–1,000.0 V
20.0–400.0 Hz
0.01–10,000.00 A
100.0–9,999.0 RPM
0.1–1,000.0
See 1-29 Automatic Motor Adaption
(AMA)
0.000–99.990
0–1,000
2–100
10–9,000
[0] Disabled
[1] Enabled
0.05–3,600.0 s
0.05–3,600.0 s
0.0–400 Hz
0.0–400 Hz
0–400
See 5-40 Function Relay
MG18A422 - VLT
Default
Function
Size related
Enter motor voltage from nameplate data
Size related
Enter motor frequency from nameplate data
Size related
Enter motor current from nameplate data
Size related
Enter motor nominal speed from nameplate data
Size related
This parameter is available only when 1-10 Motor
Construction Design is set to [1] PM, non-salient
SPM.
NOTE!
Changing this parameter will affect settings
of other parameters
Off
Performing an AMA optimizes motor performance.
Size related
Set the stator resistance value
Size related
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance cannot
be found by performing an AMA.
4
Enter the number of motor poles
Size related
Line-Line RMS back EMF voltage at 1000 RPM
When PM is selected, Flying Start is enabled and
cannot disable
0
Select [1] Enable to enable the drive to catch a
motor spinning due to line drop-out. Select [0]
Disable if this function is not required. When is
enabled 1-71 Start Delay and 1-72 Start Function
have no function. is active in VVC+ mode only.
0
The minimum reference is the lowest value
obtainable by summing all references.
50
The maximum reference is the lowest obtainable
by summing all references.
Size related
Ramp-up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected; ramp-up
time from 0 to 1-25 Motor Nominal Speed if PM
motor is selected
Size related
Ramp-down time from rated 1-23 Motor Frequency
to 0 if Asynchron motor is selected; ramp-down
time from 1-25 Motor Nominal Speed to 0 if PM
motor is selected.
0 Hz
Enter the minimum limit for low speed
65 Hz
Enter the maximum limit for high speed
Size related
Enter the maximum output frequency value
Alarm
Select the function to control output relay 1.
®
is a registered Danfoss trademark