Quick Guide
No & Name
Range
3-41 Ramp 1
0.05–3,600.0 s
Ramp Up
Time
3-42 Ramp 1
0.05–3,600.0 s
Ramp Down
Time
4-12 Motor
0.0–400 Hz
Speed Low
Limit [Hz]
4-14 Motor
0.0–400 Hz
Speed High
Limit [Hz]
4-19 Max
0–400
Output
Frequency
Table 1.28
Changes Made
Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
are listed in changes made.
If the parameter's value is changed back to the factory
setting value from another different value, the parameter
will NOT be listed in Changes Made.
1.
Press [Menu] key to enter the Quick Menu until
indicator in display is placed above Quick Menu.
2.
Press [
] [
] to select either FC 101 wizard,
closed-loop set-up, motor set-up or changes
made, then press [OK].
3.
Press [
] [
] to browse through the parameters
in the Quick Menu.
4.
Press [OK] to select a parameter.
5.
Press [
] [
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter "Status", or
press [Menu] once to enter "Main Menu".
The Main Menu accesses all parameters.
1.
Press [Menu] key until indicator in display is
placed above "Main Menu".
2.
Press [
] [
] to browse through the parameter
groups.
3.
Press [Ok] to select a parameter group.
4.
Press [
] [
] to browse through the parameters
in the specific group.
®
VLT
HVAC Basic Drive Quick Guide
Default
Function
Size related
Ramp-up time
from 0 to rated
1-23 Motor
Frequency
Size related
Ramp-down time
from rated
1-23 Motor
Frequency to 0
0.0 Hz
Enter the
minimum limit
for low speed
65
Enter the
maximum limit
for high speed
Size related
Enter the
maximum output
frequency value
®
MG18A422 - VLT
is a registered Danfoss trademark
5.
Press [Ok] to select the parameter.
6.
Press [
] [
] to set/change the parameter value.
1