Operating Guide ECL Comfort 210/296/310, application A232 / A332
The application A332.1 is very similar to the application A232.1.
Extras in relation to A232.1:
Return temperature limitation:
The return temperature S10 can be limited, for example not to
be too high (heating) or too low (cooling). If so, the desired flow
temperature at S3 can be adjusted, for example at heating to a
lower value or, at cooling to a higher value.
This results in a gradual closing of the motorized control valve.
In boiler-based heating supply the return temperature should not
be too low (same adjustment procedure as above).
The ON-OFF output X5 can be set to
follow Schedule 1 or
follow Schedule 2 or
follow Schedule 3 or
switch ON at cooling demand
Alarm A1:
An alarm activates relay 6.
Changes in relation to A332.1:
The ON-OFF output X4 can be set to
operate as a Humidistat or
operate as a switch, depending on the outdoor temperature
For a description of the change-over from heating to cooling
operation, please read the section 'A232 in general' .
8 | © Danfoss | 2017.08
Typical A332.1 application:
The shown diagram is a fundamental and simplified example and does
not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
List of components:
ECL 310
Electronic controller ECL Comfort 310
S1
Outdoor temperature sensor
S2
ECA 31 Room temperature and RH sensor *
S3
Flow temperature sensor
S4
not used
S5
(Optional) Floor surface temperature sensor
S6
(Optional) Ceiling surface temperature sensor
S7
(not illustrated) Override input for stop of circulation
pump
S8
(not illustrated) Override input for Comfort / Saving
S9
not used
S10
Return temperature sensor
P1
Circulation pump (ON / OFF)
X2
Cooling demand (ON / OFF)
X3
Heating demand (ON / OFF)
X4
(not illustrated) Multi-functionality
X5
(not illustrated) Multi-functionality
M1
Motorized control valve (3-point controlled)
M2
Motorized change-over valve
A1
Alarm
* Alternative: ESM-10, room temperature sensor
VI.JM.G2.02