Optional Function - Danfoss ECL Comfort 210 Operating Manual

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A232 / A332

5.9 Optional function

The section "Optional function" describes specific application
related issues.
Some specific functions are available under special conditions.
For example, Relay 4 (X4) can be set to change when the outdoor
temperature gets above a set value.
This section also offers a humidistat. When the measured humidity
(ECA 31) gets above a set level, the relay 4 (X4) can be activated in
order to, for example, start a dehumidifier.
Relay 5 (X5), only in ECL 310, can be set to follow one of the 3
built-in week schedules.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Optional function
Stop at T out (Stop function related to the outdoor
temperature)
When the outdoor temperature gets above the set value, the Relay 4 (X4)
goes ON.
This functionality can be used for bivalent mode, for example to stop an oil
or gas boiler and start a heat-pump.
Precondition:
The parameter ' Acc. output func. ' (Accessories, output function, ID 11089)
must be set to "2".
See Appendix "Parameter ID overview"
Value: Set the activation value
VI.JM.G2.02
'Stop at T out' , functionality:
1x038
=
X
Time
=
T
Temperature
# 1 # =
Outdoor temperature
# 2 # =
'Stop at T out' (ID 1x038)
# 3 # =
Status of Relay 4 (X4)
© Danfoss | 2017.08 | 109