Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Flow temperature / Inlet temperature
Dew p. T offset (Dew point temperature, offset)
The value calculated by the controller for the dew point temperature can be
offset adjusted (displaced). The dew point temperature is the temperature at
which water in the air condenses. If the ECA 31 is not placed correctly, it can
be useful to offset adjust the calculated dew point temperature.
See Appendix "Parameter ID overview"
Value: Set the offset value
MENU > Settings > Flow temperature / Inlet temperature
Temp. min.
See Appendix "Parameter ID overview"
Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this
setting. Adjust the factory setting, if required.
MENU > Settings > Flow temperature / Inlet temperature
Temp. max.
See Appendix "Parameter ID overview"
Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.
72 | © Danfoss | 2017.08
1x164
1x177
'Temp. min. ' is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
'Temp. min. ' can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
1x178
The setting of 'heat curve' is possible for heating circuits only.
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
VI.JM.G2.02