Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Room limit
Room T diff. (Room temperature difference for switching
cooling mode ON and OFF)
Setting the difference for room temperature in cooling mode for switching
cooling ON and OFF.
See Appendix "Parameter ID overview"
Value:
Set the difference
MENU > Settings > Room limit
Room T influence (Room temperature influence in cooling
mode)
Determination for room temperature influence when in Cooling mode.
See Appendix "Parameter ID overview"
OFF:
Room temperature has no influence for Cooling ON
/ OFF
ON:
Room temperature has influence for Cooling ON / OFF
Select the desired functionality.
74 | © Danfoss | 2017.08
1x027
=
X
Time
=
T
Temperature
# 1 # =
Actual room temperature
# 2 # =
'Room T diff.' (ID 1x027)
# 3 # =
Desired room temperature, cooling
# 4 # =
Cooling
In order to have the desired functionality, the parameter 'Room T
influence' (ID 12157) must be set to ON.
1x157
VI.JM.G2.02