Operating Guide ECL Comfort 210/296/310, application A232 / A332
A232, in general, continued
Short process descriptions:
Change from heating to cooling (outdoor and room temperature
based):
1. Heating active
2. Outdoor and room temperature rising
3. Heating stop when actual outdoor temperature gets higher
than 'Summer, cut-out' (ID 1x179)
4. Cooling start when:
Accumulated outdoor temperature value gets higher than
set limit ('Activation, acc. T' , ID 12144)
AND
Accumulated room temperature value gets higher than set
limit (' Act., acc. room T' , ID 12156)
AND
Actual room temperature gets higher than desired room
temperature for cooling operation.
Change from heating to cooling (room temperature based):
1. Heating active
2. Room temperature rising
3. Heating stop when accumulated room temperature value gets
higher than desired room temperature for heating operation.
4. Cooling start when:
Accumulated room temperature value gets higher than set
limit (' Act., acc. room T' , ID 12156)
AND
Actual room temperature gets higher than desired room
temperature for cooling operation.
VI.JM.G2.02
The controller is pre-programmed with factory settings that are shown
in the 'Parameter ID overview' appendix.
© Danfoss | 2017.08 | 13