Electrical Connections - Danfoss ECL Comfort 210 Operating Manual

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A232 / A332

2.5 Electrical connections

2.5.1 Electrical connections 230 V a.c.
The common ground terminal is used for connection of relevant
components (pumps, motorized control valves).
VI.JM.G2.02
Safety Note
Necessary assembly, start-up, and maintenance work must be
performed by qualified and authorized personnel only.
Local legislations must be respected. This comprises also cable size
and isolation (reinforced type).
A fuse for the ECL Comfort installation is max. 10 A typically.
The ambient temperature range for the ECL Comfort in operation is
0 - 55 °C. Exceeding this temperature range can result in malfunctions.
Installation must be avoided if there is a risk for condensation (dew).
ECL 210 / 310
ECL 296
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.
© Danfoss | 2017.08 | 27