5 SETTINGS
!
PATH: SETTINGS
PRODUCT SETUP
# CONTROL
# PUSHBUTTON 1
MESSAGE
The three standard pushbuttons located on the top left panel of the faceplate are user-programmable and can be used for
various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-pro-
grammable displays, etc. The location of the control pushbuttons in the following figure.
An additonal four control pushbuttons are included when the T35 is ordered with twelve user programmable pushbuttons.
The control pushbuttons are typically not used for critical operations. As such, they are not protected by the control pass-
word. However, by supervising their output operands, the user can dynamically enable or disable the control pushbuttons
for security reasons.
Each control pushbutton asserts its own FlexLogic™ operand,
configured appropriately to perform the desired function. The operand remains asserted as long as the pushbutton is
pressed and resets when the pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton
manipulation will be recognized by various features that may use control pushbuttons as inputs.
An event is logged in the Event Record (as per user setting) when a control pushbutton is pressed; no event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key
must be released before the next one can be pressed.
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL
Enabled=1
SYSTEM SETUP/
BREAKERS/BREAKER 2/
BREAKER 2 PUSHBUTTON
CONTROL
Enabled=1
GE Multilin
!"

CONTROL PUSHBUTTONS

CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
EVENTS: Disabled
STATUS
EVENT CAUSE
IN SERVICE
VOLTAGE
TROUBLE
CURRENT
RESET
TEST MODE
FREQUENCY
TRIP
OTHER
USER 1
ALARM
PHASE A
PICKUP
PHASE B
USER 2
PHASE C
NEUTRAL/GROUND
USER 3
USER 4
USER 5
USER 6
USER 7
Figure 5–3: CONTROL PUSHBUTTONS
:
AND
RUN
OFF
ON
:
Figure 5–4: CONTROL PUSHBUTTON LOGIC
T35 Transformer Management Relay
5.2.12 CONTROL PUSHBUTTONS
!
CONTROL PUSHBUTTON 1(7)
Range: Disabled, Enabled
Range: Disabled, Enabled
THREE
STANDARD
CONTROL
PUSHBUTTONS
FOUR EXTRA
OPTIONAL
CONTROL
PUSHBUTTONS
842733A2.CDR
CONTROL PUSHBTN 1(7) ON
TIMER
FLEXLOGIC OPERAND
0
CONTROL PUSHBTN 1 ON
100 msec
5.2 PRODUCT SETUP
. These operands should be
842010A2.CDR
5-29
5