Installation - GE T35 Instruction Manual

Transformer management relay
Hide thumbs Also See for T35:
Table of Contents

Advertisement

5 SETTINGS
c) UNRETURNED MESSAGES ALARM CH1(2)
!
PATH: SETTINGS
PRODUCT SETUP
# UNRETURNED
# MESSAGES ALARM CH1
MESSAGE
MESSAGE
MESSAGE
The T35 checks integrity of the direct input/output communication ring by counting unreturned messages. In the ring config-
uration, all messages originating at a given device should return within a pre-defined period of time. The Unreturned Mes-
sages Alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unreturned
messages. This function counts all the outgoing messages and a separate counter adds the messages have failed to
return. When the unreturned messages counter reaches the user-definable level specified by the
setting and within the user-defined message count
THRESHOLD
FlexLogic™ operand is set.
When the total message counter reaches the user-defined maximum specified by the
setting, both the counters reset and the monitoring process is restarted.
COUNT
The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based
output. Latching and acknowledging conditions, if required, should be programmed accordingly.
The Unreturned Messages Alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input/output messages is available as the
!"
UNRETURNED MSG COUNT CH1(2)
!
PATH: SETTINGS
PRODUCT SETUP

# INSTALLATION

#
MESSAGE
To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until
is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
RELAY SETTINGS
self-test error message is displayed until the relay is put into the "Programmed" state.
UNIT NOT PROGRAMMED
The
setting allows the user to uniquely identify a relay. This name will appear on generated reports. This name
RELAY NAME
is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com-
munications channel using the IEC 61850 protocol.
GE Multilin
!"
!"
DIRECT I/O
UNRETURNED MESSAGES ALARM CH1(2)
UNRET MSGS ALARM CH1
FUNCTION: Disabled
UNRET MSGS ALARM CH1
MESSAGE COUNT: 600
UNRET MSGS ALARM CH1
THRESHOLD: 10
UNRET MSGS ALARM CH1
EVENTS: Disabled
UNRET MSGS ALARM CH1 COUNT
actual value.
!"
INSTALLATION
RELAY SETTINGS:
Not Programmed
RELAY NAME:
Relay-1
T35 Transformer Management Relay
5.2 PRODUCT SETUP
Range: Enabled, Disabled
Range: 100 to 10000 in steps of 1
Range: 1 to 1000 in steps of 1
Range: Enabled, Disabled
UNRET MSGS ALARM CH1
, the
DIR IO CH1 UNRET ALM
UNRET MSGS ALARM CH1 MESSAGE
!
ACTUAL VALUES
STATUS
5.2.17 INSTALLATION
Range: Not Programmed, Programmed
Range: up to 20 alphanumeric characters
5
!"
DIRECT INPUTS
5-39