Outputs - GE T35 Instruction Manual

Transformer management relay
Hide thumbs Also See for T35:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break at L/R of 40 ms:
0.25 A DC max. at 48 V
0.10 A DC max. at 125 V
Operate time:
< 4 ms
Contact material:
Silver alloy
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break at L/R of 40 ms:
0.25 A DC max.
Operate time:
< 4 ms
Contact material:
Silver alloy
Control:
separate operate and reset inputs
Control mode:
operate-dominant or reset-dominant
FORM-A VOLTAGE MONITOR
Applicable voltage:
approx. 15 to 250 V DC
Trickle current:
approx. 1 to 2.5 mA
FORM-A CURRENT MONITOR
Threshold current:
approx. 80 to 100 mA
FORM-C AND CRITICAL FAILURE RELAY
Make and carry for 0.2 s: 10 A
Carry continuous:
6 A
Break at L/R of 40 ms:
0.25 A DC max. at 48 V
0.10 A DC max. at 125 V
Operate time:
< 8 ms
Contact material:
Silver alloy
FAST FORM-C RELAY
Make and carry:
0.1 A max. (resistive load)
Minimum load impedance:
INPUT
IMPEDANCE
VOLTAGE
2 W RESISTOR
250 V DC
20 KΩ
120 V DC
5 KΩ
48 V DC
2 KΩ
24 V DC
2 KΩ
Note: values for 24 V and 48 V are the same due to a
required 95% voltage drop across the load impedance.
Operate time:
< 0.6 ms
Internal Limiting Resistor: 100 Ω, 2 W
GE Multilin
SOLID-STATE OUTPUT RELAY
Operate and release time: <100 µs
Maximum voltage:
Maximum continuous current: 5 A at 45°C; 4 A at 65°C
Make and carry for 0.2 s: as per ANSI C37.90
Breaking capacity:
Operations/
interval
Break
capability
(0 to 250 V
DC)
IRIG-B OUTPUT
Amplitude:
Maximum load:
Time delay:
Isolation:
CONTROL POWER EXTERNAL OUTPUT
(FOR DRY CONTACT INPUT)
Capacity:
Isolation:
REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)
Standard output points: 32
User output points:
DIRECT OUTPUTS
1 W RESISTOR
Output points:
50 KΩ
DCMA OUTPUTS
2 KΩ
Range:
2 KΩ
Max. load resistance:
2 KΩ
Accuracy:
99% Settling time to a step change: 100 ms
Isolation:
Driving signal:
Upper and lower limit for the driving signal: –90 to 90 pu in steps of
T35 Transformer Management Relay
2.2 SPECIFICATIONS

2.2.7 OUTPUTS

265 V DC
IEC 647-5 / UL508
Utility
application
(autoreclose
scheme)
5 ops /
5000 ops /
0.2 s-On,
1 s-On, 9 s-Off
0.2 s-Off
within 1
1000 ops /
minute
0.5 s-On, 0.5 s-Off
3.2 A
L/R = 10 ms
1.6 A
10 A
L/R = 20 ms
L/R = 40 ms
0.8 A
L/R = 40 ms
10 V peak-peak RS485 level
100 ohms
1 ms for AM input
40 µs for DC-shift input
2 kV
100 mA DC at 48 V DC
±300 Vpk
32
32
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
12 kΩ for –1 to 1 mA range
12 kΩ for 0 to 1 mA range
600 Ω for 4 to 20 mA range
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
1.5 kV
any FlexAnalog quantity
0.001
2
Industrial
application
10000 ops /
0.2 s-On,
30 s-Off
10 A
L/R = 40 ms
2-9