The T35 Transformer Management Relay has been designed to provide primary protection for medium to high voltage
power transformers. It performs this function on a variety of power transformer configurations with up to six sets of three
phase inputs available.
b) GENERAL TRANSFORMER SETTINGS
!"
PATH: SETTINGS
SYSTEM SETUP
# GENERAL
#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The general transformer settings apply to all windings. Settings specific to each winding are shown in the following section.
GE Multilin
!
!
SETTING GROUP 1(6)
# GENERAL
#
# WINDING 1
#
# WINDING 2
#
# WINDING 3
#
# WINDING 4
#
# WINDING 5
#
# WINDING 6
#
!"
!
TRANSFORMER
GENERAL
NUMBER OF WINDINGS:
2
REFERENCE WINDING:
Automatic Selection
PHASE COMPENSATION:
Internal (software)
LOAD LOSS AT RATED
LOAD:
100 kW
RATED WINDING TEMP
RISE: 65°C (oil)
NO LOAD LOSS:
10 kW
TYPE OF COOLING:
OA
TOP-OIL RISE OVER
AMBIENT:
35°C
THERMAL CAPACITY:
100.00 kWh/°C
WINDING THERMAL TIME
CONSTANT: 2.00 min
T35 Transformer Management Relay
TRANSFORMER
See page 5–45.
See page 5–47.
See page 5–47.
See page 5–47.
See page 5–47.
See page 5–47.
See page 5–47.
Range: 2 to 6 in steps of 1
Range: Automatic Selection, Winding 1, Winding 2,...,
Winding 6
Range: Internal (software), External (with CTs)
Range: 1 to 20000 kW in steps of 1
Range: 55°C (oil), 65°C (oil), 80°C (dry), 115°C (dry),
150°C (dry)
Range: 1 to 20000 kW in steps of 1
Range: OA, FA, Non-directed FOA/FOW, Directed FOA/
FOW
Range: 1 to 200°C in steps of 1
Range: 0.00 to 200.00 kWh/°C in steps of 0.01
Range: 0.25 to 15.00 min. in steps of 0.01