MAINTENANCE

ERROR MESSAGES

An error message identifies a possible instrument failure and requires an action. The error message will be displayed on the unit and/or
selected on the Pactware screen while the output signal will shift to the selected error output (3.6mA, 22mA or HOLD).
Display
Action
Message
HiVolAlm
Verify strapping table is entered correctly.
SlopeErr
Consult factory
LoopFail
Consult factory
Note: In case of loop failure, error signal will follow the failing trend;
meaning the unit will show 3.6 mA when the reviewed loop current by
the device is found too low. The unit will show 22 mA in case the
reviewed loop current is found too high.
No Ramp
Consult factory
DfltParm
Consult factory
EE Fail
Consult factory
CPU Fail
Consult factory
SfwrFail
Consult factory
EOP < Probe
Length
1) Ensure probe length is entered correctly
2) Set transmitter to a lower dielectric range
3) Set threshold to «fixed»
4) Consult factory
Lvl < Probe
Length
1) Verify entered probe length
2) Change threshold to «fixed»
EOP High
1) Ensure probe length is entered correctly
2) Increase blocking distance (only for single or twin GWR probes)
3) Consult factory
NoSignal
1) Ensure dielectric setting is correct for measured medium
2) Increase sensitivity
3) Confirm that the probe type is proper for the dielectric of the medium
4) Consult factory
No Fid
1) Check connection between probe and transmitter
2) Check for moisture on top of probe
3) Check for damaged gold pin on the high frequency connector
4) Consult factory
FidShift
1) Check connection between probe and transmitter
2) Check for moisture on top of probe
3) Check for damaged gold pin on the high frequency connector
4) Consult factory
No Probe
1) Ensure proper connection between probe and transmitter
2) Check for damaged gold pin on the high frequency connector
SZ Alarm
When in «SZ Fault», «Latch 3.6 mA» or «Latch 22 mA» was
Decrease level in tank
selected, reset with «SZ Alarm Reset»
Comment
Level more than 5% above
highest point in strapping table.
Ramp circuit generating
improper voltage
Loop current differs from
expected value
No End-of-Ramp signal detect-
ed
Internal non-volatile parameters
have been defaulted
EEPROM error allowing watch-
dog timer to expire
A-D converter time out allowing
watchdog timer to expire
A fatal software error allowing
watchdog timer to expire
End of Probe signal is out of
range
Apparent position of the upper
level pulse is lower than the
end of probe
End of Probe signal is out of
range
No level signal being detected.
Fiducial signal is not being
detected
FidTicks shifted from expected
value
Electronics does not sense that
a probe is attached
Safety Zone alarm has been
tripped, loop current fixed at
SZ Fault