MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface & Volume
Screen
BlockDis
24
x.x
SZ Fault
25
(select)
SZHeight
26
xx.x
SZ Alarm
27
Reset
Threshld
28
IfcThrsh
29
(select)
Poll Adr
3
xx
Loop Mode
31
Trim Lvl
32
xx.x
Trim 4
33
xxxx
Trim 20
34
xxxx
Loop Tst
35
xx.x mA
LvlTicks
36
xxxxx
IfcTicks
37
xxxx
Medium
38
New Pass
39
xxx
Language
4
Mdl705HT
41
Ver xx.xx
DispFact
42
(select)
Strapping table
NOTE: Consult page 17 for level offset «Lvl Ofst» details.
Action
Enter distance in
selected level units
Select the safety zone fault.
Select the safety zone value
Reset safety zone latch fault
Select top level threshold.
Select interface threshold.
Enter HART ID number.
Enable/Disable
Enter value
to adjust level reading.
Fine tune the 4 mA point.
Fine tune the 20 mA point.
Enter a mA output value.
Diagnostic display.
Diagnostic display.
Diagnostic display.
Enter new password.
Select language
None, do not adjust.
Advanced diagnostics.
max. Pt 20 Vol = ...... l
Pt 4 Vol = 3000 l
Pt 3 Vol = 2000 l
Pt 2 Vol = 1000 l
Pt 1 Vol =       0 l
Comment
Allows to ignore level measurements near the top of the probe,
caused by e.g. condensation, crystalization. Make sure that the liquid
level does NOT enter this zone. Consult factory or the
'Troubleshooting' section before entering any value. Normaly to be
used with single rod probe.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or
«Latch 22mA». When either «Latch 3.6 / 22mA» signals is
selected, the loop current remains in alarm until it is manually reset
with the «SZAlarm» reset screen ( for safety zone explanation see
Terminology - page 11).
Enter safety zone in cm or inches (see Terminology - page 11).
Clear a latched safety zone alarm «SZFault».
Default selection for most common applications is «Fixed».
Default selection for all applications is «CFD». In case the unit does
not track the correct interface layer, select «Fixed».
Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
Determines whether the loop is fixed at 4.0 mA or controlled by the
PV.
Allows to compensate for a fixed level deviation.
Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Set mA Output to any given value to perform loop test .
Shows time of flight from fiducial pulse to reflected signal from level.
Shows time of flight through the upper liquid layer.
Shows type of detected upper liquid; unknown «Unknown» oil only
«Oil Only», thin oil layer «Thin Oil», thick oil layer «Thick
Oil» or no level «Dry Probe».
Use arrows to select desired value. Values between 0 and 255.
Select «English», «Français», «Deutsch» or «Espagnol».
Factory setting. «Ver» refers to software version.
See page 20.
max. Pt 20 Lvl = ...... cm
Pt 4 Lvl = 200 cm
Pt 3 Lvl = 120 cm
Pt 2 Lvl =   50 cm
Pt 1 Lvl =     0 cm
19