Eclipse 705 Installation And Operating Manual page 15

Guided wave radar level transmitter
Table of Contents

Advertisement

MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level & Volume
Screen
BlockDis
21
x.x
SZ Fault
22
(select)
SZHeight
23
xx.x
SZ Alarm
24
Reset
Threshld
25
(select)
Poll Adr
26
xx
Loop Mode
27
Trim Lvl
28
xx.x
Trim 4
29
xxxx
Trim 20
3
xxxx
Loop Tst
31
xx.x mA
LvlTicks
32
xxxxx
New Pass
33
xxx
Language
34
Mdl705HT
35
Ver xx.xx
DispFact
36
(select)
Strapping table
NOTE: Consult page 13 for level offset «Lvl Ofst» details.
Action
Enter distance in
selected level units
Select the safety zone fault.
Select the safety zone value
Reset safety zone latch fault
Select the type of threshold
Enter HART ID number.
Enable/Disable
Enter value
to adjust level reading.
Fine tune the 4 mA point.
Fine tune the 20 mA point.
Enter a mA output value.
Diagnostic display.
Enter new password.
Select language
None, do not adjust.
Advanced diagnostics.
max. Pt 20 Vol = ...... l
Pt 4 Vol = 3000 l
Pt 3 Vol = 2000 l
Pt 2 Vol = 1000 l
Pt 1 Vol =       0 l
Comment
Allows to ignore level measurements near the top of the probe,
caused by e.g. condensation, crystalization. Make sure that the liquid
level does NOT enter this zone. Consult factory or the
'Troubleshooting' section before entering any value. Normaly to be
used with single rod probe.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or
«Latch 22mA». When either «Latch 3.6 / 22mA» signals is
selected, the loop current remains in alarm until it is manually reset
with the «SZAlarm» reset screen ( for safety zone explanation see
Terminology - page 11).
Enter safety zone in cm or inches (see Terminology - page 11).
Select «Reset» «No» or «Yes» to reset alam when either «Latch
3.6mA» or «Latch 22mA» was selected in «SZFault».
«Fixed» = the first reflection from the top will be considered as level
(default setting)
«CFD» = the strongest reflection from the top will be considered as
level.
Only change to «CFD», in case the unit is reading incorrect level.
Adjustment of trim level «Trim Lvl» may be necessary when
threshold is changed.
Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
Determines whether the loop is fixed at 4.0 mA or controlled by the
PV.
Allows to compensate for a fixed level deviation.
Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Set mA Output to any given value to perform loop test.
Shows time of flight from fiducial pulse to reflected signal from level.
Use arrows to select desired value. Values between 0 and 255.
Select «English», «Français», «Deutsch» or «Espagnol».
Factory setting. «Ver» refers to software version.
See page 20.
max. Pt 20 Lvl = ...... cm
Pt 4 Lvl = 200 cm
Pt 3 Lvl = 120 cm
Pt 2 Lvl =   50 cm
Pt 1 Lvl =     0 cm
15