Eclipse 705 Installation And Operating Manual page 18

Guided wave radar level transmitter
Table of Contents

Advertisement

MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface & Volume
Screen
*Status*
1
*IfcVol*
*%Output*
*Loop*
IfcLevel
2
or Ifc Vol
%Output
3
xx.x%
Loop
4
xx.xx mA
IfcLvl
5
xxxx
Volume
6
xx.x
Level
7
xxxx
PrbModel
8
(select)
PrbMount
9
(select)
MeasType
1
(select)
LvlUnits
11
(select)
Probe Ln
12
xxx.x
Lvl Ofst
13
xxx.x
VolUnits
14
StrapTbl
15
xx pnts
Upr Diel
16
(Select)
Dielctrc
17
(Select)
Senstvty
18
xxx
Loop Ctrl
19
(Select)
Set 4mA
2
xxx.x
Set 20mA
21
xxx.x
Damping
22
xx s
Fault
23
(Select)
18
Action
Transmitter Display
Transmitter Display
Transmitter Display
Transmitter Display
Transmitter Display
Transmitter Display
Transmitter Display
Select the type of probe
Select the type of probe
mounting.
Select the type of measurement
Select units for level
Enter the exact length of
probe.
Enter the offset value.
Select units for volume.
Enter level/volume
pairs in max 20 steps
Enter the dielectric range
value of the upper media.
Select the dielectric range
value of the lower media
Enter sensitivity value
Select primary variable (PV)
Enter the level value
for the 4 mA point.
Enter the level value
for the 20 mA point.
Enter the damping factor.
Enter the value for error.
= Quick Start up
Comment
Transmitter default values cycle every 5 seconds. Status «Status»,
Interface volume «IfcVolume», % Output «% Output», and Loop
«Loop».
Transmitter displays Interface volume or Interface level in selected
engineering units (depending selection in Loop control «Loop Ctrl»
Transmitter displays % Output measurement derived from 20 mA
span.
Transmitter displays Loop measurement (mA).
Transmitter displays interface level in selected level units
«LvlUnits».
Transmitter displays volume in selected volume units «VollUnits».
Transmitter displays level in selected level units «LvlUnits».
Select as per the 3 first digits of the probe partnumber. The partnumber
is shown on the nameplate: e.g. 705-510A-A11/7MT-A230-218, select
7xT-x from the list.
Select NPT «NPT», BSP «BSP» or Flange «Flange».
ry when a
«7xK» GWR probe is used)
Select interface - volume «IfcVol».
cm «cm», m «m», inches «inches» or feet «feet».
Enter as per the 3 last digits of the probe partnumber on the nameplate:
- rigid probes, enter value cm or inches,
- flexible probes, enter value in meters or feet
e.g. 705-510A-A11/7MR-A230-218, enter «218» cm probe length.
When entering configuration values from the end of the probe is
cumbersome, an offset can be introduced to determine a new
reference point. This reference point can be either below the probe
(positive offset) or at the probe (negative offset). See page 11
"Terminology".
Liters «l» or gallons «g».
Liters «l» or gallons «g».
Enter the dielectrics of the upper layer liquid (between 1,4 and 5,0) –
only upper layer dielectrics need to be entered.
Select: «10–100»
Allows fine adjustment of internal gain.
Primary variable is the loop controlling parameter. Select inter-
face level
«IfcLevel» or interface volume «Ifc Vol»
A transition zone may exist at the bottom of the probe. See Functional
Specifications Probe, see page 34 and continuing.
A transition zone / blocking distance may exist at the top of the probe.
See Functional Specifications Probe, page 34 and continuing.
A damping factor (1-10 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of
loop failure, error signal will follow the failing trend; meaning the unit
will show 3.6 mA when the reviewed loop current by the device is
found too low. The unit will show 22 mA in case the reviewed loop
current is found too high.
(consult facto-

Advertisement

Table of Contents

Troubleshooting

loading