MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level only
Screen
BlockDis
18
xx.x
SZ Fault
19
(select)
SZHeight
2
xx.x
SZ Alarm
21
Reset
Threshld
22
(select)
Poll Adr
23
xx
Loop Mode
24
Trim Lvl
25
xx.x
Trim 4
26
xxxx
Trim 20
27
xxxx
Loop Tst
28
xx.x mA
LvlTicks
29
xxxxx
New Pass
3
xxx
Language
31
Mdl705HT
32
Ver xx.xx
DispFact
33
(select)
OFFSET
75 cm
15 cm
10 cm
Action
Enter distance in
selected level units
Select the safety zone fault.
Select the safety zone value
Reset safety zone latch fault
Select the type of threshold
Enter HART ID number.
Enable/Disable
Enter value
to adjust level reading.
Fine tune the 4 mA point.
Fine tune the 20 mA point.
Enter a mA output value.
Diagnostic display.
Enter new password.
Select language
None, do not adjust.
Advanced diagnostics.
No offset
(Offset at 0 cm)
100 %
20 mA = 75 cm
0 %
4 mA = 15 cm
Comment
Allows to ignore level measurements near the top of the probe,
caused by e.g. condensation, crystalization. Make sure that the liquid
level does NOT enter this zone. Consult factory or the
'Troubleshooting' section before entering any value. Normaly to be
used with single rod probe.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or
«Latch 22mA». When either «Latch 3.6 / 22mA» signals is
selected, the loop current remains in alarm until it is manually cleared
with the «SZAlarm» screen ( for safety zone explanation see
Terminology - page 11).
Enter safety zone in cm or inches (see Terminology - page 11).
Clear a latched safety zone alarm «SZFault».
«Fixed» = the first reflection from the top will be considered as level
(default setting)
«CFD» = the strongest reflection from the top will be considered as
level.
Only change to «CFD», in case the unit is reading incorrect level.
Adjustment of trim level «Trim Lvl» may be necessary when
threshold is changed.
Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
Determines whether the loop is fixed at 4.0 mA or controlled by the
PV.
Allows to compensate for a fixed level deviation.
Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Set mA Output to any given value to perform loop test .
Shows time of flight from fiducial pulse to reflected signal from level.
Use arrows to select desired value. Values between 0 and 255.
Select «English», «Français», «Deutsch» or «Espagnol».
Factory setting. «Ver» refers to software version.
See page 20.
Positive offset
Negative offset
(Offset at 10 cm)
(Offset at -15 cm)
20 mA = 85 cm
4 mA = 25 cm
20 mA = 60 cm
4 mA = 0 cm
13