Eclipse 705 Installation And Operating Manual page 17

Guided wave radar level transmitter
Table of Contents

Advertisement

MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface
Screen
BlockDis
2
x.x
SZ Fault
21
(select)
SZHeight
22
xx.x
SZ Alarm
23
Reset
Threshld
24
IfcThrs
25
(select)
Poll Adr
26
xx
Loop Mode
27
Trim Lvl
28
xx.x
Trim 4
29
xxxx
Trim 20
3
xxxx
Loop Tst
31
xx.x mA
LvlTicks
32
xxxxx
IfcTicks
33
xxxx
Medium
34
New Pass
35
xxx
Language
36
Mdl705HT
37
Ver xx.xx
DispFact
38
(select)
OFFSET
75 cm
15 cm
10 cm
Action
Enter distance in
selected level units
Select the safety zone fault.
Select the safety zone value
Reset safety zone latch fault
Select top level threshold.
Select interface threshold.
Enter HART ID number.
Enable/Disable
Enter value
to adjust level reading.
Fine tune the 4 mA point.
Fine tune the 20 mA point.
Enter a mA output value.
Diagnostic display.
Diagnostic display.
Diagnostic display.
Enter new password.
Select language
None, do not adjust.
Advanced diagnostics.
No offset
(Offset at 0 cm)
100 %
20 mA = 75 cm
0 %
4 mA = 15 cm
Comment
Allows to ignore level measurements near the top of the probe,
caused by e.g. condensation, crystalization. Make sure that the liquid
level does NOT enter this zone. Consult factory or the
'Troubleshooting' section before entering any value. Normaly to be
used with single rod probe.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or
«Latch 22mA». When either «Latch 3.6 / 22mA» signals is
selected, the loop current remains in alarm until it is manually reset
with the «SZAlarm» reset screen ( for safety zone explanation see
Terminology - page 11).
Enter safety zone in cm or inches (see Terminology - page 11).
Clear a latched safety zone alarm «SZFault».
Default selection for most common applications is «Fixed».
Default selection for all applications is «CFD». In case the unit does
not track the correct interface layer, select «Fixed».
Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
Determines whether the loop is fixed at 4.0 mA or controlled by the
PV.
Allows to compensate for a fixed level deviation.
Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Set mA Output to any given value to perform loop test .
Shows time of flight from fiducial pulse to reflected signal from level.
Shows time of flight through the upper liquid layer.
Shows type of detected upper liquid; unknown «Unknown» oil only
«Oil Only», thin oil layer «Thin Oil», thick oil layer «Thick
Oil», or no level «Dry Probe».
Use arrows to select desired value. Values between 0 and 255.
Select «English», «Français», «Deutsch» or «Espagnol».
Factory setting. «Ver» refers to software version.
See page 20.
Positive offset
(Offset at 10 cm)
20 mA = 85 cm
4 mA = 25 cm
Negative offset
(Offset at -15 cm)
20 mA = 60 cm
4 mA = 0 cm
17