32
Dispenser on Hold. (No fuel will be dispensed).
The following End of Sale indicators are applicable to dispensers running in temperature compensation, fast fill,
or PED modes:
20
The pressure at the first measurement was within 20 bar of
the calculated maximum pressure.
21
The pressure at the second measurement exceeded the
calculated maximum pressure.
22
The pressure at the third measurement exceeded the
calculated maximum pressure.
26
Twin pressure sensor values (when fitted) do not agree.
Compac Industries Ltd.
Check for blockage in the fuel delivery hose,
breakaway or vehicle pipework.
Check for blockage in the fuel delivery hose,
breakaway or vehicle pipework.
Check for blockage in the fuel delivery hose,
breakaway or vehicle pipework.
Check pressure sensor calibration.
Page 124