Supported Abb Solutions - ABB RED615 Product Manual

Line differential protection and control
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Line Differential Protection and Control
RED615
Product version: 4.0
In
figure 7
uncoordinated auto-reclosing attempts
are prevented by means of binary signal transfer
(BST). During the auto-reclosing sequence a
"wait" command is sent to the auto-reclosing
function of the lower circuit breaker and thereby
blocking the function. The upper circuit breaker is

5. Supported ABB solutions

ABB's 615 series protection and control IEDs
together with the Grid Automation controller
COM600 constitute a genuine IEC 61850 solution
for reliable power distribution in utility and
industrial power systems. To facilitate and
streamline the system engineering ABB's IEDs are
supplied with Connectivity Packages containing a
compilation of software and IED-specific
information including single-line diagram
templates, a full IED data model including event
and parameter lists. By utilizing the Connectivity
Packages the IEDs can be readily configured via
the PCM600 Protection and Control IED Manager
and integrated with the Grid Automation controller
COM600 or the MicroSCADA Pro network control
and management system.
The 615 series IEDs offer native support for the
IEC 61850 standard also including binary and
analog horizontal GOOSE messaging. Compared
with traditional hard-wired inter-device signaling,
peer-to-peer communication over a switched
Ethernet LAN offers an advanced and versatile
platform for power system protection. Fast
software-based communication, continuous
supervision of the integrity of the protection and
communication system, and inherent flexibility for
reconfiguration and upgrades are among the
distinctive features of the protection system
approach enabled by the full implementation of
the IEC 61850 substation automation standard.
At the substation level COM600 uses the data
content of the bay level IEDs to offer enhanced
Table 3. Supported ABB solutions
Product
Grid Automation controller COM600
MicroSCADA Pro SYS 600
System 800xA
14
thereafter closed by its auto-reclosing function.
This blocking signal is reset after successful auto-
reclosing of the upper circuit breaker, enabling
the lower breaker to be closed by its auto-
reclosing function.
substation level functionality. COM600 features a
web-browser based HMI providing a
customizable graphical display for visualizing
single line mimic diagrams for switchgear bay
solutions. The SLD feature is especially useful
when 615 series IEDs without the optional single
line diagram feature are used. Further, the web
HMI of COM600 offers an overview of the whole
substation, including IED-specific single line
diagrams, thus enabling convenient information
accessibility. To enhance personnel safety, the
web HMI also enables remote access to
substation devices and processes. Furthermore,
COM600 can be used as a local data warehouse
for technical documentation of the substation and
for network data collected by the IEDs. The
collected network data facilitates extensive
reporting and analyzing of network fault situations
using the data historian and event handling
features of COM600. The data historian can be
used for accurate process performance
monitoring by following process and equipment
performance calculations with real-time and
history values. Better understanding of the
process behaviour by joining time-based process
measurements with production and maintenance
events helps the user in understanding the
process dynamics.
COM600 also features gateway functionality
providing seamless connectivity between the
substation IEDs and network-level control and
management systems such as MicroSCADA Pro
and System 800xA
Version
3.5 or later
9.3 FP1 or later
5.0 Service Pack 2
1MRS756500 F
ABB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 615 series