Table 9. Energizing inputs
Description
Rated frequency
Current inputs
Rated current, I
Thermal withstand capability:
• Continuously
• For 1 s
Dynamic current withstand:
• Half-wave value
Input impedance
Voltage inputs
Rated voltage
Voltage withstand:
• Continuous
• For 10 s
Burden at rated voltage
1)
Residual current and/or phase current
Table 10. Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption
Threshold voltage
Reaction time
Table 11. Signal output X100: SO1
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant L/
R<40 ms
Minimum contact load
24
Value
50/60 Hz
n
4 A
100 A
250 A
<100 mΩ
60...210 V AC
240 V AC
360 V AC
<0.05 VA
Value
±20% of the rated voltage
24...250 V DC
1.6...1.9 mA
31.0...570.0 mW
18...176 V DC
3 ms
Value
250 V AC/DC
5 A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
1MRS756500 F
1)
1/5 A
20 A
500 A
1250 A
<20 mΩ