16. Access control

To protect the IED from unauthorized access and
to maintain information integrity, the IED is
provided with a four-level, role-based
authentication system with administrator-
programmable individual passwords for the
viewer, operator, engineer and administrator level.
The access control applies to the front-panel user
interface, the web-browser based user interface
and the PCM600 tool.

17. Inputs and outputs

Depending on the standard configuration
selected, the IED is equipped with three phase-
current inputs and one residual-current input for
non-directional earth-fault protection and current
circuit supervision, or three phase-current inputs,
one residual-current input and one residual
Fibre-optic line differential
communication link
Protection communication and supervision
Binary signal transfer
Pilot wire line differential
modem
communication link
Protection communication and supervision
Binary signal transfer
RPW600
modem
voltage input for directional earth-fault protection
and current circuit supervision.
The phase-current inputs are rated 1/5 A. Two
optional residual-current inputs are available, i.e.
1/5 A or 0.2/1 A. The 0.2/1 A input is normally
used in applications requiring sensitive earth-fault
protection and featuring core-balance current
transformers. The residual-voltage input covers
the rated voltages 60-210 V.
The phase-current input 1 A or 5 A, the residual-
current input 1 A or 5 A, alternatively 0.2 A or 1 A,
and the rated voltage of the residual voltage input
are selected in the IED software. In addition, the
binary input thresholds 18...176 V DC are
selected by adjusting the IED's parameter
settings.