Table 34. Directional earth-fault protection (DEFxPDEF)
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0
1)
Set
x I
, f
= 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
n
n
measurements
2)
Includes the delay of the signal output contact
Start value = 2.5 x I
Start value multiples in range of 1.5 to 20
3)
Maximum
,
n
36
DEFLPDEF
DEFHPDEF
DEFHPDEF
I
= 2 x set
Start value
Fault
DEFLPDEF
Start value
I
= 2 x set
Fault
Value
Depending on the frequency of the current measured: f
±2 Hz
Current:
±1.5% of the set value or ±0.002 x I
Voltage
±1.5% of the set value or ±0.002 x U
Phase angle:
±2°
Current:
±1.5% of the set value or ±0.002 x I
(at currents in the range of 0.1...10 x I
±5.0% of the set value
(at currents in the range of 10...40 x I
Voltage:
±1.5% of the set value or ±0.002 x U
Phase angle:
±2°
Minimum
Typical
42 ms
44 ms
61 ms
64 ms
< 40 ms
Typical 0.96
< 30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n x f
, where n = 2, 3, 4, 5,...
n
Peak-to-Peak: No suppression
1MRS756500 F
n
n
n
n
)
n
)
n
n
Maximum
46 ms