Motor Protection and Control
REM615
Product version: 5.0 FP1
GUID-1D463521-838D-4518-BFE5-438DD6F8E0A8 V1 EN
Figure 6.
Motor protection and control of contactor and circuit breaker controlled motors using standard configuration D
Example of motor protection and control of contactor and
circuit breaker controlled motors using standard configuration
D is shown in
Figure
6. In this configuration current sensors
(Rogowski coil) and voltage sensors (voltage divider) are used
for the measurements. To prevent possible power system
instability due to busbar voltage collapse, the simultaneous
starting of several motors can be inhibited with the "restart

5. Supported ABB solutions

The 615 series protection relays together with the Substation
Management Unit COM600S constitute a genuine IEC 61850
solution for reliable power distribution in utility and industrial
power systems. To facilitate the system engineering, ABB's
relays are supplied with connectivity packages. The
connectivity packages include a compilation of software and
relay-specific information, including single-line diagram
ABB
Io
3U
3I
3I
3U
Io
RTD
REM615
Std. conf.
D
ANSI
IEC
37
3I<
46R
I2>>
47O-/59
U2>/3U>
47U+/27
U1</3U<
49,66,48,51LR
Is2t n<
49M
3Ith>M
50L/50NL
ARC
50P/51P
3I>>>
51LR
Ist>
51P/51N
3I/Io
inhibit" input of REM615. The optional RTD/mA inputs are
utilized for motor winding and bearing temperature supervision.
The standard configuration D has been pre-configured
especially for ABB switchgears, for example, UniGear Digital.
The use of this configuration is not restricted for that purpose
only.
templates and a full relay data model. The data model includes
event and parameter lists. With the connectivity packages, the
relays can be readily configured using PCM600 and integrated
with COM600S or the network control and management
system MicroSCADA Pro.
The 615 series relays offer native support for IEC 61850 Edition
2 also including binary and analog horizontal GOOSE
REF615
Std. conf.
L
ANSI
IEC
47O-/59
U2>/3U>
47U+/27
U1</3U<
50L/50NL
ARC
50P/51P
3I>>>
51BF/51NBF
3I>/Io>BF
67
3I→
3I
3U
Io
RTD
REM615
Std. conf.
D
ANSI
IEC
37
3I<
46R
I2>>
47O-/59
U2>/3U>
47U+/27
U1</3U<
49,66,48,51LR
Is2t n<
49M
3Ith>M
50L/50NL
ARC
50P/51P
3I>>>
51LR
Ist>
51P/51N
3I/Io