KEB Combivert R6 Instruction Manual page 41

Power supply and regenerative unit
Hide thumbs Also See for Combivert R6:
Table of Contents

Advertisement

Operation of the Unit
No.
Name
CP.21
Last error
CP.22
Last error -1
CP.23
Last error -2
CP.24
Last error -3
CP.25
Last error -4
CP.26
Last error -5
CP.27
Last error -6
CP.28
Last error -7
Parameters CP.21... 28 display the last eight errors which occur. With exception error "un-
dervoltage E.UP" is not stored. The oldest error is displayed in CP.28. A new error is stored
in CP.21. All other errors are shifted to the next parameter. The oldest error (CP.28) is not
applicable.
The meaning of the error messages is described in parameter CP.1.
No.
Name
CP.29
Software version
Value range
0.00...9.99
No.
Name
CP.30
Software date
Value range
0...6553.5
No.
Name
CP.31
Power unit identification
The COMBIVERT R6-S detects the connected supply system (230 V/400 V) at the first swit-
ching on. Depending on the supply system the COMBIVERT R6-S adjusts internally certain
parameter values.
If the COMBIVERT R6-S connected to another supply system, these stored parameter va-
lues are not correct any longer. Error message "power unit changed (E.Puch)" is displayed.
Value range
0...32767
No.
Name
CP.32
Puls off level
Value range
0.0...-1000.0 kW
GB - 42
Meaning
Display of the inverter software version number (e.g. 1,11).
Meaning
Display of the inverter software date in the format „ddmm.y".
Meaning
If the displayed value is written, only the power unit dependent parame-
ters are re-initialised. By writing of any other value error E.Puch is reset
and the default values are loaded. Now the COMBIVERT R6-S reacts
like a first switching on.
default
Meaning
If the adjusted regenerative power is decreased, the COM-
-0.8 kW
BIVERT R6-S switches the modulation off after turn-off de-
lay and changes into standby mode (display: „Stb").
r/w
Enter
Yes
r/w
Enter
Origin
In.24 set 0
In.24 set 1
In.24 set 2
In.24 set 3
In.24 set 4
In.24 set 5
In.24 set 6
In.24 set 7
r/w
Enter
r/w
Enter
r/w
Enter
Origin
cS.06
Origin
In.06
Origin
In.07
Origin
SY.3

Advertisement

Table of Contents
loading

Table of Contents