KEB Combivert R6 Instruction Manual page 37

Power supply and regenerative unit
Hide thumbs Also See for Combivert R6:
Table of Contents

Advertisement

Operation of the Unit
No.
Name
CP.01
Status display
Error ! Interior temperature, temperature in the interior > 95 °C
E.OHI
Error ! Overload, overload monitoring of the regenerative unit has responded
E. OL
Error ! Overvoltage, DC link voltage too high
E. OP
„Error in power unit", power unit code is missing, load shunt relay defective
E. Pu
Power unit identification invalid
E.Puci
Error ! Power unit changed, a configured unit for 400 V was connected to a 230 V
mains (or reverse). Load factory setting with CP.31, so the unit can adapt itself to
E.Puch
the changed supply system.
Error ! Synchronization, phase allocation at commutation reactor not correct
E.SYn
Error ! Undervoltage, DC link voltage too low
E. UP
No.
Name
CP.02
Actual line frequency
After switching on the actual line frequency is determined during the initialization phase.
Slowly changes of the line frequency during the operation are recognized and displayed
in CP.02. CP.02 displays the actual regenerative frequency, if the COMBIVERT R6-S is in
"netof" status.
Resolution
0.01 Hz
No.
Name
CP.03
AC current L1
CP.04
AC current L2
CP.05
AC current L3
Resolution
0.1 A
No.
Name
CP.06
Actual DC utilization
Resolution
1 %
GB - 38
Meaning
positive values = clockwise rotating field
negative values = counterclockwise rotating field
Meaning
Display of the actual input current of the respective phase.
Meaning
Independent whether power supply or regenerative operation, the dis-
play indicates the actual utilization of the COMBIVERT R6-S. 100 % cor-
respond to the rated current of the COMBIVERT R6-S.
r/w
Enter
Origin
ru.00
r/w
Enter
Origin
ru.03
r/w
Enter
Origin
ru.08
ru.09
ru.10
r/w
Enter
Origin
ru.13