5.2 PRODUCT SETUP
EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any
data from the T60 memory map can be configured to be included in an EGD exchange. The settings are the starting
Modbus register address for the data item in decimal format. Refer to Appendix B for the complete Modbus memory
map. Note that the Modbus memory map displays shows addresses in hexadecimal format; as such, it will be neces-
sary to convert these values to decimal format before entering them as values for these setpoints.
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.
That is, for items occupying more than one Modbus register (e.g. 32 bit integers and floating point values), only the first
5
Modbus address is required. The EGD exchange configured with these settings contains the data items up to the first
setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid Modbus
addresses and the fourth is 0, the produced EGD exchange will contain three data items.
PATH: SETTINGS

MODBUS USER MAP

The Modbus User Map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
ADDRESS
played in the
VALUE
lines incremented by "1". An address value of "0" in the initial register means "none" and values of "0" will be dis-
ADDRESS
played for all registers. Different
5-28
Courtesy of NationalSwitchgear.com
PRODUCT SETUP
MODBUS USER MAP
ADDRESS
VALUE:
ADDRESS
MESSAGE
VALUE:
ADDRESS 256:
MESSAGE
VALUE:
line (this value must be converted from hex to decimal format). The corresponding value is dis-
line. A value of "0" in subsequent register
values can be entered as required in any of the register positions.
ADDRESS
T60 Transformer Management Relay
Range: 0 to 65535 in steps of 1
1:
0
0
Range: 0 to 65535 in steps of 1
2:
0
0
Range: 0 to 65535 in steps of 1
0
0
lines automatically returns values for the previous
ADDRESS
5 SETTINGS
5.2.5 MODBUS USER MAP