Advertisement

5.5 GROUPED ELEMENTS
c) PHASE OVERVOLTAGE (ANSI 59P)
PATH: SETTINGS
PHASE
OVERVOLTAGE1
5
The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a definite
time element. The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal-
culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below.
SETTING
PHASE OV1
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
PHASE OV1
BLOCK:
Off = 0
SETTING
PHASE OV1
SOURCE:
Source VT = Delta
VAB
VBC
VCA
Source VT = Wye
5-134
Courtesy of NationalSwitchgear.com
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE OV1
FUNCTION: Disabled
PHASE OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE OV1
MESSAGE
PICKUP: 1.000 pu
PHASE OV1 PICKUP
MESSAGE
DELAY:
PHASE OV1 RESET
MESSAGE
DELAY:
PHASE OV1 BLOCK:
MESSAGE
Off
PHASE OV1
MESSAGE
TARGET: Self-reset
PHASE OV1
MESSAGE
EVENTS: Disabled
SETTING
PHASE OV1
PICKUP:
RUN
VAB PICKUP
AND
RUN
VBC
PICKUP
RUN
VCA PICKUP
Figure 5–65: PHASE OVERVOLTAGE SCHEME LOGIC
T60 Transformer Management Relay
VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: FlexLogic™ Operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTINGS
PHASE OV1 PICKUP
DELAY:
PHASE OV1 RESET
DELAY:
t PKP
t RST
t PKP
t RST
t PKP
t RST
5 SETTINGS
PHASE OVERVOLTAGE1
FLEXLOGIC OPERANDS
PHASE OV1 A PKP
PHASE OV1 A DPO
PHASE OV1 A OP
PHASE OV1 B PKP
PHASE OV1 B DPO
PHASE OV1 B OP
PHASE OV1 C PKP
PHASE OV1 C DPO
PHASE OV1 C OP
FLEXLOGIC OPERAND
OR
PHASE OV1 OP
FLEXLOGIC OPERAND
AND
PHASE OV1 DPO
FLEXLOGIC OPERAND
OR
PHASE OV1 PKP
827066A7.CDR
GE Multilin