GE T60 Instruction Manual page 275

Ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS
The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as
ing equation is applied:
where: x is a driving signal specified by the
I
and I
are defined by the
min
max
k is a scaling constant calculated as:
The feature is intentionally inhibited if the
< 0.1 pu. The resulting characteristic is illustrated in the following figure.
VAL
The dcmA output settings are described below.
DCMA OUTPUT F1 SOURCE: This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving dcmA outputs. Refer to Appendix A for a complete list of FlexAnalog parameters.
DCMA OUTPUT F1 RANGE: This setting allows selection of the output range. Each dcmA channel may be set inde-
pendently to work with different ranges. The three most commonly used output ranges are available.
DCMA OUTPUT F1 MIN VAL: This setting allows setting the minimum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current (see the following
examples). The setting is entered in per-unit values. The base units are defined in the same manner as the FlexEle-
ment™ base units.
DCMA OUTPUT F1 MAX VAL: This setting allows setting the maximum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current (see the following
examples). The setting is entered in per-unit values. The base units are defined in the same manner as the FlexEle-
ment™ base units.
The
DCMA OUTPUT F1 MIN VAL
the
DCMA OUTPUT F1 SOURCE
NOTE
Three application examples are described below.
GE Multilin
Courtesy of NationalSwitchgear.com
and
match the output range of the hardware defined as
MIN VAL
MAX VAL
I
if x
<
MIN VAL
min
>
I
if x
I
MAX VAL
=
max
out
(
)
k x
MIN VAL
+
setting
SOURCE
setting
RANGE
I
max
k
------------------------------------------------ -
=
MAX VAL
and
MAX VAL
MIN VAL
I
max
I
min
DRIVING SIGNAL
MIN VAL
Figure 5–92: DCMA OUTPUT CHARACTERISTIC
and
DCMA OUTPUT F1 MAX VAL
is set to FlexAnalog value based on power factor measurement).
T60 Transformer Management Relay
5.8 TRANSDUCER INPUTS/OUTPUTS
I
otherwise
min
I
min
MIN VAL
settings are entered incorrectly, e.g. when
MAX VAL
842739A1.CDR
settings are ignored for power factor base units (i.e. if
. The follow-
RANGE
(EQ 5.50)
5
(EQ 5.51)
MAX VAL
MIN
5-179