5.2 PRODUCT SETUP
b) DIGITAL CHANNELS
PATH: SETTINGS
DIGITAL CHANNELS
5
A
DIGITAL CHANNEL
oscillography trace depends in part on the number of parameters selected here. Parameters set to "Off" are ignored. Upon
startup, the relay will automatically prepare the parameter list.
c) ANALOG CHANNELS
PATH: SETTINGS
ANALOG CHANNELS
An
ANALOG CHANNEL
lography trace depends in part on the number of parameters selected here. Parameters set to "Off" are ignored. The
parameters available in a given relay are dependent on: (a) the type of relay, (b) the type and number of CT/VT hardware
modules installed, and (c) the type and number of Analog Input hardware modules installed. Upon startup, the relay will
automatically prepare the parameter list. A list of all possible analog metering actual value parameters is presented in
Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to expedite the
selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of parameters via the
relay keypad/display - entering this number via the relay keypad will cause the corresponding parameter to be displayed.
All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-
nates the IB signal on Terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules,
no analog traces will appear in the file; only the digital traces will appear.
The source harmonic indices appear as oscillography analog channels numbered from 0 to 23. These correspond
directly to the to the 2nd to 25th harmonics in the relay as follows:
NOTE
Analog channel 0 ↔ 2nd harmonic
Analog channel 1 ↔ 3rd harmonic
...
Analog channel 23 ↔ 25th harmonic
5-32
Courtesy of NationalSwitchgear.com
PRODUCT SETUP
OSCILLOGRAPHY
DIGITAL CHANNEL
Off
DIGITAL CHANNEL 63:
MESSAGE
Off
setting selects the FlexLogic™ operand state recorded in an oscillography trace. The length of each
PRODUCT SETUP
OSCILLOGRAPHY
ANALOG CHANNEL 1:
Off
ANALOG CHANNEL 16:
MESSAGE
Off
setting selects the metering actual value recorded in an oscillography trace. The length of each oscil-
T60 Transformer Management Relay
DIGITAL CHANNELS
Range: FlexLogic™ operand
1:
Range: FlexLogic™ operand
ANALOG CHANNELS
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.