C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup-
software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to
the IEC 61850 IED Configuration section later in this appendix).
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
C
general steps required for transmission configuration are:
1.
Configure the transmission dataset.
2.
Configure the GOOSE service settings.
3.
Configure the data.
The general steps required for reception configuration are:
1.
Configure the reception dataset.
2.
Configure the GOOSE service settings.
3.
Configure the data.
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1.
Configure the transmission dataset by making the following changes in the
IEC 61850 PROTOCOL
GOOSE 1
CONFIG GSE 1 DATASET ITEMS
Set
to "GGIO1.ST.Ind1.q" to indicate quality flags for GGIO1 status indication 1.
ITEM 1
Set
to "GGIO1.ST.Ind1.stVal" to indicate the status value for GGIO1 status indication 1.
ITEM 2
The transmission dataset now contains a set of quality flags and a single point status Boolean value. The reception
dataset on the receiving device must exactly match this structure.
2.
Configure the GOOSE service settings by making the following changes in the
IEC 61850 PROTOCOL
URABLE GOOSE 1
Set
CONFIG GSE 1 FUNCTION
Set
CONFIG GSE 1 ID
Set
CONFIG GSE 1 DST MAC
Set the
CONFIG GSE 1 VLAN PRIORITY
Set the
CONFIG GSE 1 VLAN ID
Set the
CONFIG GSE 1 ETYPE APPID
configuration on the receiver (the default value is "0").
Set the
CONFIG GSE 1 CONFREV
this example it can be left at its default value.
3.
Configure the data by making the following changes in the
COL
GGIO1 STATUS CONFIGURATION
Set
GGIO1 INDICATION 1
a contact input, virtual input, a protection element status, etc.).
The T60 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
C-8
Courtesy of NationalSwitchgear.com
GSSE/GOOSE CONFIGURATION
settings menu:
GSSE/GOOSE CONFIGURATION
settings menu:
to "Enabled".
to an appropriate descriptive string (the default value is "GOOSEOut_1").
to a multicast address (for example, 01 00 00 12 34 56).
; the default value of "4" is OK for this example.
value; the default value is "0", but some switches may require this value to be "1".
value. This setting represents the Ethertype application ID and must match the
value. This value changes automatically as described in IEC 61850 part 7-2. For
settings menu:
to a FlexLogic™ operand used to provide the status of GGIO1.ST.Ind1.stVal (for example,
T60 Transformer Management Relay
PRODUCT SETUP
TRANSMISSION
CONFIGURABLE GOOSE
PRODUCT SETUP
TRANSMISSION
CONFIGURABLE GOOSE
PRODUCT SETUP
COMMUNICATION
APPENDIX C
COMMUNICATION
CONFIGURABLE
COMMUNICATION
CONFIG-
IEC 61850 PROTO-
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents