7.15 Position Sensor Abnormality

H6
Error Code
Outdoor Unit LED
A
Display
Method of Error
A compressor start-up failure is detected by checking the compressor running condition through the
position detection circuit.
Detection
Error Decision
Conditions
Supposed
Causes
Service Diagnosis
j
i
i
h
h
1
2
3
4
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Power supply voltage out of specification
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage is outside the specified range.
h
5
Troubleshooting for Outdoor Unit