CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions

2.10 POWERFUL Operation

Outline
In order to exploit the cooling and heating capacity to full extent, the air conditioner can be operated
by increasing the indoor fan rotating speed and the compressor frequency.
Details
When POWERFUL button is pressed, the fan speed and target temperature are converted to the
following states for 20 minutes.
Operation mode
COOL
DRY
HEAT
FAN
AUTO
A
Ex: POWERFUL operation in cooling
Note:
POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW or
OUTDOOR UNIT QUIET operation.
54
Dry rotating speed + A rpm
Same as cooling/heating in
= 50 ~ 90 rpm (depending on the model)
Target temp.
18˚C (64.4˚F)
POWERFUL
ON
POWERFUL
OFF
Fan
A rpm
H tap
Set tap
Fan speed
H tap + A rpm
H tap + A rpm
H tap + A rpm

POWERFUL operation

Lower limit of cooling
temperature
20 minutes
Target temperature
18°C (64.4°F)
Lowered by 2 ~ 2.5°C
(3.6 ~ 4.5°F)
30 ~ 31.5°C (86 ~ 88.7°F)
The target temperature is
kept unchanged.
Remote controller registers
20 minutes independently.
Ending condition:
1. Lapse of 20 minutes
2. System operation OFF
3. POWERFUL operation OFF
Functions and Control
SiUS121630EA
(R24589)