Thermistor Or Related Abnormality (Outdoor Unit) - Daikin CTXG09QVJUW Service Manual

Multi-split type air conditioners 2/3/4mxs-n series
Hide thumbs Also See for CTXG09QVJUW:
Table of Contents

Advertisement

SiUS121630EA

7.17 Thermistor or Related Abnormality (Outdoor Unit)

H9 , J3 , J6 , J8 , J9 , P4
Error Code
Outdoor Unit LED
A
Display
Method of Error
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Detection
Error Decision
Conditions
Supposed
Causes
In case of P4
Troubleshooting
Replace the outdoor unit PCB (main PCB).
P4
Service Diagnosis
j
i
i
h
h
1
2
3
4
The voltage between the both ends of the thermistor is above 4.96 V or below 0.04 V with the
power on.
J3
error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
The system is shut down if all the units are judged as the J8 error.
Disconnection of the connector for the thermistor
Thermistor corresponding to the error code is defective.
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger thermistor
in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
: Radiation fin thermistor
h
5
Troubleshooting for Outdoor Unit
185