Indoor Fan Motor Connector Check; Hall Ic Check - Daikin CTXG09QVJUW Service Manual

Multi-split type air conditioners 2/3/4mxs-n series
Hide thumbs Also See for CTXG09QVJUW:
Table of Contents

Advertisement

Check
8.2

Indoor Fan Motor Connector Check

Check No.02
CTXG, CTXS, FTXS, FVXS Series
1. Check the connection of connector.
2. Check motor power supply voltage output (pins 4 - 7).
3. Check motor control voltage (pins 4 - 3).
4. Check rotation command voltage output (pins 4 - 2).
5. Check rotation pulse input (pins 4 - 1).
FFQ Series
1. Check the connection of connector.
2. Check motor power supply voltage output (pins 5 - 8).
3. Check motor control voltage (pins 5 - 4).
4. Check rotation command voltage output (pins 5 - 3).
8.3

Hall IC Check

Check No.04
CDXS, FDXS Series
1. Check the connector connection.
2. With the power on, operation off, and the connector connected, check the following.
192
S1 or S200
7
6
5
4
3
2
1
X20A
8
7
6
5
4
3
2
1
(1) Output voltage of about 5 V between pins 1 and 3.
(2) Generation of 3 pulses between pins 2 and 3 when the indoor fan motor is operating.
If NG in step (1)
Defective PCB
If NG in step (2)
Defective Hall IC
If OK in both steps (1) and (2)
Motor power supply voltage (310 ~ 340 VDC)
Unused
Unused
GND
Motor control voltage (15 VDC)
Rotation command voltage (1~ 5 VDC)
Rotation pulse input
Motor power supply voltage (290 ~ 330 VDC)
Unused
Unused
GND
Motor control voltage (15 VDC)
Rotation command voltage (0 ~ 5 VDC)
Rotation pulse input
Unused
Replace the PCB (control PCB).
Replace the indoor fan motor.
Replace the PCB (control PCB).
S7
Gray (power supply)
1
2
Purple (signals)
3
Blue (grounding)
SiUS121630EA
(R14225)
(R24373)
(R14211)
Service Diagnosis