6 ACTUAL VALUES
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn,
and VOn. For form-C contact outputs, the state is displayed as Off or On.
NOTE
PATH: ACTUAL VALUES
STATUS
 VIRTUAL OUTPUTS
MESSAGE
MESSAGE
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, 'Virt Op 1' refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
a) STATUS
PATH: ACTUAL VALUES
STATUS
 REMOTE DEVICES
 STATUS
MESSAGE
MESSAGE
MESSAGE
The present state of the programmed remote devices is shown here. The
whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required
remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES
STATUS
 REMOTE DEVICE
1
MESSAGE
Statistical data (two types) for up to 32 programmed remote devices is shown here.
The
number is obtained from the indicated remote device and increments whenever a change of state of at least
STNUM
one item occurs in the GSSE/GOOSE message. The
increments whenever a GSSE/GOOSE message, without a state change, is sent. When the GSSE/GOOSE message
trasmits a state change, the
mented.
GE Multilin


VIRTUAL OUTPUTS

Virt Op
1
Off
Virt Op
2
Off
Virt Op 96
Off

REMOTE DEVICES STATUS
All REMOTE DEVICES
ONLINE: No
REMOTE DEVICE
STATUS: Offline
REMOTE DEVICE
STATUS: Offline
REMOTE DEVICE 32
STATUS: Offline

REMOTE DEVICES STATISTICS
REMOTE DEVICE
StNum:
REMOTE DEVICE
SqNum:
SQNUM
resets to 0. This number rolls over to zero when a count of 4,294,967,295 is incre-
SQNUM
C30 Controller System
Range: On, Off
Range: On, Off
Range: On, Off
Range: Yes, No
Range: Online, Offline
1
Range: Online, Offline
2
Range: Online, Offline
ALL REMOTE DEVICES ONLINE
REMOTE DEVICE 1(32)
1
0
1
0
number is obtained from the indicated remote device and
6.2 STATUS
6.2.7 VIRTUAL OUTPUTS

6.2.8 REMOTE DEVICES

message indicates
6-5