GE C30 Instruction Manual page 340

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 12 of 48)
ADDR
REGISTER NAME
3E39
Field Shared Output 1 Channel Dest 1
3E3A
Field Shared Output 1 Unit Dest 2
3E3B
Field Shared Output 1 Channel Dest 2
3E3C
Field Shared Output 1 Events
3E3D
...Repeated for Field Shared Output 2
3E4A
...Repeated for Field Shared Output 3
3E57
...Repeated for Field Shared Output 4
3E64
...Repeated for Field Shared Output 5
3E71
...Repeated for Field Shared Output 6
3E7E
...Repeated for Field Shared Output 7
B
3E8B
...Repeated for Field Shared Output 8
3E98
...Repeated for Field Shared Output 9
3EA5
...Repeated for Field Shared Output 10
3EB2
...Repeated for Field Shared Output 11
3EBF
...Repeated for Field Shared Output 12
3ECC
...Repeated for Field Shared Output 13
3ED9
...Repeated for Field Shared Output 14
3EE6
...Repeated for Field Shared Output 15
3EF3
...Repeated for Field Shared Output 16
Field Unit RTDs (Read/Write Setting) (8 modules)
3F00
Field Unit RTD 1Name
3F06
Field Unit RTD 1 Origin
3F07
Field Unit RTD 1 Type
3F08
...Repeated for Field Unit RTD 2
3F10
...Repeated for Field Unit RTD 3
3F18
...Repeated for Field Unit RTD 4
3F20
...Repeated for Field Unit RTD 5
3F28
...Repeated for Field Unit RTD 6
3F30
...Repeated for Field Unit RTD 7
3F38
...Repeated for Field Unit RTD 8
Field Unit Transducers (Read/Write Setting) (8 modules)
3F40
Field Unit Transducer 1 Name
3F46
Field Unit Transducer 1 Origin
3F47
Field Unit Transducer 1 Range
3F48
Field Unit Transducer 1 Min Value
3F4A
Field Unit Transducer 1 Max Value
3F4C
Field Unit Transducer 1 Units
3F4F
...Repeated for Field Unit Transducer 2
3F5E
...Repeated for Field Unit Transducer 3
3F6D
...Repeated for Field Unit Transducer 4
3F7C
...Repeated for Field Unit Transducer 5
3F8B
...Repeated for Field Unit Transducer 6
3F9A
...Repeated for Field Unit Transducer 7
3FA9
...Repeated for Field Unit Transducer 8
Field Unit Identifiers (Read Only) (8 modules)
3FB8
Attached Field Unit 1 Serial Number
3FBE
Attached Filed Unit 1 Port Number
3FBF
Attached Field Unit 1 Type
3FC0
Field Unit 1 Status
3FC1
...Repeated for Field Unit 2
3FCA
...Repeated for Field Unit 3
3FD3
...Repeated for Field Unit 4
3FDC
...Repeated for Field Unit 5
B-20
RANGE
1 to 15
0 to 8
1 to 15
0 to 1
0 to 1
0 to 24
0 to 2
0 to 1
0 to 24
0 to 9
-9999.999 to 9999.999
-9999.999 to 9999.999
---
---
---
0 to 3
0 to 4
C30 Controller System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
---
1
F256
---
1
F001
---
1
F102
---
1
F205
---
1
F253
---
1
F259
---
1
F205
---
1
F253
---
1
F246
---
0.001
F004
---
0.001
F004
---
---
F206
---
1
F205
---
1
F001
---
1
F243
---
1
F262
DEFAULT
1
0 (None)
1
1 (Enabled)
"RTD 1"
0 (None)
0 (100 Ohm
Nickel)
"TRD 1"
0 (None)
6 (0...20mA)
0
100000
(none)
(none)
0
0 (CC-05)
0 (Disabled)
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents