B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 30 of 48)
ADDR
REGISTER NAME
IEC 61850 LN Name Prefixes (Read/Write Settings)
AB48
IEC 61850 Logical Node LPHD1 Name Prefix
AB4B
IEC 61850 Logical Node PIOCx Name Prefix (72 items)
AC23
IEC 61850 Logical Node PTOCx Name Prefix (24 items)
AC6B
IEC 61850 Logical Node PTUVx Name Prefix (13 items)
AC92
IEC 61850 Logical Node PTOVx Name Prefix (10 items)
ACB0
IEC 61850 Logical Node PDISx Name Prefix (10 items)
ACCE
IEC 61850 Logical Node RBRFx Name Prefix (24 items)
AD16
IEC 61850 Logical Node RPSBx Name Prefix
AD19
IEC 61850 Logical Node RRECx Name Prefix (6 items)
B
AD2B
IEC 61850 Logical Node MMXUx Name Prefix (6 items)
AD3D
IEC 61850 Logical Node GGIOx Name Prefix (5 items)
AD4C
IEC 61850 Logical Node RFLOx Name Prefix (5 items)
AD5B
IEC 61850 Logical Node XCBRx Name Prefix (6 items)
AD6D
IEC 61850 Logical Node PTRCx Name Prefix (6 items)
AD7F
IEC 61850 Logical Node PDIFx Name Prefix (4 items)
AD8B
IEC 61850 Logical Node MMXNx Name Prefix (37 items)
ADFA
IEC 61850 Logical Node CSWIx Name Prefix (30 items)
AE54
IEC 61850 Logical Node XSWIx Name Prefix (24 items)
IEC 61850 GGIO4 General Analog Configuration Settings (Read/Write Setting)
AF00
Number of Analog Input Points in GGIO4
IEC 61850 GGIO4 Analog Input Points Configuration Settings (Read/Write Setting) (32 modules)
AF10
IEC 61850 GGIO4 Analog Input 1 Value
AF11
IEC 61850 GGIO4 Analog Input 1 Deadband
AF13
IEC 61850 GGIO4 Analog Input 1 Minimum
AF15
IEC 61850 GGIO4 Analog Input 1 Maximum
AF17
...Repeated for IEC 61850 GGIO4 Analog Input 2
AF1E
...Repeated for IEC 61850 GGIO4 Analog Input 3
AF25
...Repeated for IEC 61850 GGIO4 Analog Input 4
AF2C
...Repeated for IEC 61850 GGIO4 Analog Input 5
AF33
...Repeated for IEC 61850 GGIO4 Analog Input 6
AF3A
...Repeated for IEC 61850 GGIO4 Analog Input 7
AF41
...Repeated for IEC 61850 GGIO4 Analog Input 8
AF48
...Repeated for IEC 61850 GGIO4 Analog Input 9
AF4F
...Repeated for IEC 61850 GGIO4 Analog Input 10
AF56
...Repeated for IEC 61850 GGIO4 Analog Input 11
AF5D
...Repeated for IEC 61850 GGIO4 Analog Input 12
AF64
...Repeated for IEC 61850 GGIO4 Analog Input 13
AF6B
...Repeated for IEC 61850 GGIO4 Analog Input 14
AF72
...Repeated for IEC 61850 GGIO4 Analog Input 15
AF79
...Repeated for IEC 61850 GGIO4 Analog Input 16
AF80
...Repeated for IEC 61850 GGIO4 Analog Input 17
AF87
...Repeated for IEC 61850 GGIO4 Analog Input 18
AF8E
...Repeated for IEC 61850 GGIO4 Analog Input 19
AF95
...Repeated for IEC 61850 GGIO4 Analog Input 20
AF9C
...Repeated for IEC 61850 GGIO4 Analog Input 21
AFA3
...Repeated for IEC 61850 GGIO4 Analog Input 22
AFAA
...Repeated for IEC 61850 GGIO4 Analog Input 23
AFB1
...Repeated for IEC 61850 GGIO4 Analog Input 24
AFB8
...Repeated for IEC 61850 GGIO4 Analog Input 25
AFBF
...Repeated for IEC 61850 GGIO4 Analog Input 26
AFC6
...Repeated for IEC 61850 GGIO4 Analog Input 27
AFCD
...Repeated for IEC 61850 GGIO4 Analog Input 28
B-38
RANGE
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
4 to 32
---
0.001 to 100
–1000000000000 to
1000000000000
–1000000000000 to
1000000000000
C30 Controller System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
4
F001
---
---
F600
%
0.001
F003
---
0.001
F060
---
0.001
F060
DEFAULT
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
4
0
100000
0
1000000
GE Multilin