5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
 ANALOG INPUT / MME
 POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the C30 is restarted.
NOTE
k) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 61850 PROTOCOL
5
The C30 Controller System is provided with optional IEC 61850 communications capability. This feature is
specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for addi-
tional details.
5-36

COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off

COMMUNICATIONS
 GSSE / GOOSE
 CONFIGURATION
 SERVER
MESSAGE
 CONFIGURATION
 IEC 61850 LOGICAL
MESSAGE
 NODE NAME PREFIXES
 MMXU DEADBANDS
MESSAGE
 GGIO1 STATUS
MESSAGE
 CONFIGURATION
 GGIO2 CONTROL
MESSAGE
 CONFIGURATION
 GGIO4 ANALOG
MESSAGE
 CONFIGURATION
 GGIO5 UINTEGER
MESSAGE
 CONFIGURATION
 REPORT CONTROL
MESSAGE
 CONFIGURATION
 XCBR
MESSAGE
 CONFIGURATION
 XSWI
MESSAGE
 CONFIGURATION
C30 Controller System

DNP / IEC104 POINT LISTS
Range: any FlexAnalog parameter
0
Range: any FlexAnalog parameter
1
Range: any FlexAnalog parameter
255

IEC 61850 PROTOCOL
5 SETTINGS

ANALOG INPUT / MME POINTS