Operation of the Unit
CP.34
Control angle
This parameter adjusts the conduction angle during regen mode. By lowering this value, the audible sound
from the commutation choke can be reduced.
For the Size 19 unit: The default value is 22.0 degrees if using a commutation choke or 29.0 degrees if
using a harmonic fi lter. The typical adjustment range is 20.0-30.0 degrees with the choke and 28.0-33.0
degrees with the harmonic fi lter. Values lower than 20.0 degrees with the choke may begin to limit the
available regen power. Values higher than 36.0 and lower than 27.0 with the fi lter can result in random E.OC
errors.
For the Size 15 unit: This unit has a default value of 20.0 degrees with the commutation choke and 29.0
degrees with harmonic fi lter.
CP.35
Input Type
This parameter adjusts the inputs for the type of signals; PNP (sourcing) or NPN (sinking).